CBL
HOT
WATER BOILER DUAL CONTROL VALVE

APPLICATIONS:
When installed
in a boiler water supply line, assures automatic filling and maintains
boiler pressure between 14 and 30 psi.
SIZES: 1/2" only
FEATURES:
All
bronze construction, inbuilt monel strainer screen, phosphor bronze
diaphragms, stainless steel body seat, renewable relief seat disc.
Includes an inbuilt check valve to retard reverse flow and an
inbuilt bypass for rapid filling, high pressure tests and system
purging. Reduced pressure setting of 14 psi and relief setting
of 28 psi for two-story buildings; slightly higher setting for
3-, 4-, or 5-story buildings. Maximum inlet pressure is 200 psi.
Combines a pressure reducing and regulating valve, positive relief
valve and bypass valve into one compact unit.
NOTE: FOR BACKFLOW PREVENTION OF BOILER
WATER INTO THE POTABLE WATER SUPPLY LINE, INSTALL A BFP VALVE.
FOR
MORE INFORMATION, WRITE OR CALL
FOR BULLETIN
HYD.
CQ-M
SERIES
DUAL CONTROL VALVE FOR COMPETITIVE INSTALLATIONS

APPLICATIONS:
Designed for
hot water space heating installations.
SIZES: 1/2" only
FEATURES:
Bronze
body features large unrestricted waterways, special heat resistant
composition diaphragms, silicone relief seat, and an easy to clean
inbuilt brass strainer. All units have a test lever and an inbuilt
check valve to prevent backflow. Provides pressure control and
protection from thermal expansion.
NOTE:
THE RELIEF SECTION OF ALL CASH-ACME DUAL CONTROLS IS FOR THERMAL
EXPANSION ONLY. FOR PROPER PRESSURE RELIEF PROTECTION, THE BOILER
MUST ALSO BE PROVIDED WITH A PROPERLY SIZED ASME-RATED RELIEF
VALVE.
FOR MORE INFORMATION, WRITE OR CALL
FOR BULLETIN HYD.
CR
SERIES
DUAL CONTROL VALVE FOR HOT WATER SPACE HEATING BOILERS

APPLICATIONS:
Designed
for hot water space heating installations, the CR Series valve
is suitable for 1-, 2-, or 3-story buildings without adjustment.
SIZES: 1/2" only
FEATURES:
Balanced piston for closer outlet pressure control regardless
of variations in inlet pressure and a rapid fill feature with
an improved larger seat for higher capacities and quicker fill.
Has an iron body, brass internal parts on the regulator, special
heat resistant composition diaghragm and 0-rings, brass strainer
screen, and stainless steel springs. Relief valve has bronze body,
silicone seat disc and stainless steel spring.
FOR MORE INFORMATION, WRITE OR CALL
FOR BULLETIN HYD.